We had a false alarm go off in the building where I work last week. The elevators automatically shut down forcing the use of the fire escapes. The building is 22 floors. I was lucky in that I’d just taken the elevator to the first floor to step outside on a break. When they finally let us back in, I wondered what someone with mobility issues is expected to do had the building been on fire. Just die? Have a kind soul carry them? With most people wfh at least a couple of days per week, this seems really dangerous for anyone who might get stranded.

  • ...m...@ttrpg.network
    link
    fedilink
    arrow-up
    25
    ·
    edit-2
    5 months ago

    …architect here: we design protected areas of refuge where mobilty-impared occupants can shelter in place until emergency services arrive to evacuate them from the facility…

    …you’ll often see areas of refuge identified near elevator lobbies and equipped with hardened callboxes for emergency communication, or marked on the evacuation plan if they’re in a remote location…sometimes areas of refuge are pretty subtle if you don’t know to look for them: we design protected firewalls, structure, and building systems integrated into the facility so the biggest tells are usually callboxes, magnetic door hold-opens, or tracks for automatic fire curtains…

    …when renovating older facilities, we do the best we can to modernise life safety within the limitations of existing infrastructure, but the general rule of thumb is that as long as you’ve improved upon what originally previously existed, you’ve satisfied your obligation even if it’s not at parity with new construction…

    (it’s not uncommon for old facilities to have gone through a dozen or more life-safety modernisations since the advent of modern building codes, just palimpsested one-over-the-other as standards progressed)

    • some_guy@lemmy.sdf.orgOP
      link
      fedilink
      arrow-up
      5
      ·
      5 months ago

      Thanks so much for the info. I’m curious if you know about when these practices became common. The building I’m in for work, for example, has carpet in the hallways that looks like it was installed in the late 90s-2000s. The style of the outside seems to fit this range. Would you expect to see some, most, or all of these techniques in a building from that era? (This is in Cali, so likely early to apply the regulations I would think.)

      • ...m...@ttrpg.network
        link
        fedilink
        arrow-up
        2
        ·
        edit-2
        5 months ago

        …that’d take a deep dive into obsolete building codes to identify exactly when the concept was first introduced: BOCA, southern/standard, and uniform building codes all merged into IBC about twenty-five years ago so we’re talking about old paper code books from twentieth century…

        …areas of refuge are closely tied to modern accessibility standards which arose from the ADA in 1990; i’m guessing they were widely introduced sometime in that decade, possibly earlier for high-rises or hazardous occupancies, but they were definitely part of 1997 UBC (which most of california enforced) and 2000 IBC…

        (i started working professionally in 1993 and every project i worked on was fully accessible, but adoption varied across different jurisdictions and when i worked in california a decade later they were waaaay less accessible than texas)